Product overview
A 3 phase generator for sale should be selected as part of the site's electrical distribution system, not as an isolated engine rating. Three-phase motors, welders, pumps, compressors, ovens and mixed single-phase circuits can place very different demands on the alternator. The practical starting point is a circuit schedule showing running current, starting method and the loads that may operate together.
Kaichen can configure open, weather-protected or sound-attenuated sets for a defined voltage and frequency. The review also checks phase balance, neutral requirements, breaker arrangement, cable entry and the connection method to the main or emergency board. Published figures in this sheet are reference values for comparison; the order technical agreement controls the final product.
Reference Configuration
The table uses a published 35 kVA sound-attenuated set as a comparison point. It is not a universal offer: phase voltage, earthing, motor starting, ambient derating and the selected engine-alternator package must be confirmed for each enquiry.
|
Parameter |
Reference Value |
|
Standby reference |
35 kVA / 28 kW |
|
Prime reference |
31 kVA / 25 kW |
|
Electrical system |
380/220 V, 50 Hz, three phase, four wire |
|
Reference speed |
1500 rpm |
|
Main protection reference |
3-pole MCCB |
|
Full-load fuel benchmark |
6.25 L/h under the cited configuration |
|
Sound benchmark |
85 dB(A) at 7 m for the cited soundproof version |
|
Final selection |
Confirmed from load study and destination electrical standard |
Match the Generator to the Distribution System
- Confirm whether the site uses a three-wire or four-wire system and whether single-phase branch loads require a neutral.
- State the nominal line-to-line and line-to-neutral voltages rather than relying only on a country name.
- Provide the earthing arrangement and the purchaser's protection philosophy so neutral treatment and protective devices can be coordinated.
- Identify nonlinear equipment, sensitive controls and harmonic-producing loads that may influence alternator sizing.
Starting Current and Phase Balance
- Direct-on-line motors may create a short, high current demand. Star-delta starters, soft starters and variable-frequency drives change that starting profile and should be listed separately.
- Single-phase circuits distributed across a three-phase board should be balanced as closely as practical. A heavily loaded phase can reach its limit before the generator's total kW rating is used.
- Where several motors start automatically, a staged sequence can reduce the required transient capacity and improve voltage recovery.
Typical Buyers and Use Cases
- Fabrication shops with welding and cutting equipment
- Farms using irrigation pumps, grain handling or refrigeration
- Commercial properties with three-phase lifts, fans or chillers
- Construction compounds and temporary distribution boards
- Small factories with mixed motor and lighting loads
- Remote utilities and service workshops
Information Needed for a Three-Phase Quotation
- Required line voltage, frequency, phase, neutral and earthing arrangement
- Load list with running kW or current for each major item
- Largest motor rating, starter type and permitted voltage dip
- Simultaneous-load and future-expansion allowance
- Prime or standby operating duty
- Open, canopy, trailer or container installation preference
- Ambient temperature, altitude, dust level and acoustic limit
Product and Manufacturing Images




Factory Assembly and Project Review

Jiangsu Kaichen Electric Power Equipment Co., Ltd. manufactures generator sets and integrated power solutions for industrial, commercial and standby applications. Before production, the project team reviews the confirmed electrical rating, operating duty, installation environment, controls, enclosure and requested options. Inspection and testing scope are agreed for the actual supply package.
Frequently Asked Questions
Request a Configuration Review
Send the load list, voltage and frequency, operating duty, site conditions, enclosure preference, fuel-runtime target and control requirements. Kaichen will prepare a project configuration for technical confirmation before quotation or production.
Hot Tags: 3 phase generator for sale, China 3 phase generator for sale manufacturers, suppliers, factory, Construction Equipment Diesel Generator, Containerized 50kVA Diesel Generator, Fuel Efficient Industrial Diesel Generator, Harsh Environment Diesel Generator, industrial diesel generator set, Trailer Mounted 50Hz Diesel Generator