Product overview
The Data Center Critical Load Diesel Generator delivers G3-class transient response and certified ISO-8528 compliance, ensuring immediate, 10-second backup power to secure zero-downtime operations for critical IT infrastructures.
Technical Parameters
|
Performance Metric |
Specification Data |
|
Data Center Continuous Power (DCP) |
2500 kVA / 2000 kWe |
|
Emergency Standby Power (ESP) |
2750 kVA / 2200 kWe |
|
Rated Voltage & Frequency Options |
4160V / 13800V (Medium Voltage) 480V / 400V (Low Voltage) |
|
Engine Configuration & Displacement |
V16 Cylinder, 4-Stroke, Turbocharged, Aftercooled |
|
Transient Response Category |
G3 Class Compliance |
|
Fuel Consumption (100% DCP Load) |
512.4 L/hr (135.3 Gal/hr) |
|
Cooling Package Airflow Capacity |
3150 m³/min (111,241 CFM) |
|
Governor & Fuel System Control |
Full Authority Digital Engine Control (FADEC) |
|
Alternator Thermal Temperature Rise |
105°C Class F Rise / Class H Insulation |
|
Total Weight (Dry / Wet) |
18,450 kg / 19,120 kg |
|
Physical Dimensions (L x W x H) |
6,850 mm × 2,420 mm × 2,980 mm |
Uptime Institute Tier Compliance Matrix
|
Engineering Parameter |
Tier III Standard |
Tier IV Standard |
Factory Design Verification |
|
Power Distribution |
Single active, redundant alternate path ($N+1$). |
Dual active paths operating simultaneously ($2N$). |
Dual independent terminal boxes supporting separate A/B routing. |
|
System Isolation |
Individual components isolated without interrupting critical load. |
Structural compartmentalization prevents localized fault propagation. |
Motorized draw-out circuit breakers with isolated control wiring. |
|
Cooling Power |
Engine-driven mechanical cooling or backup electrical fans. |
Redundant cooling pathways with automated failover logic. |
Dual-source 24V DC control power preventing single-source loss. |
|
Fuel Redundancy |
Onsite storage supports 12-hour continuous rated load. |
Dual-path fuel delivery allowing concurrent maintenance. |
Dual-port manifolds with isolation valves for inline replacement. |
|
Control Logic |
Automated unit-level starting controls via serial bus. |
Isolated control networks with optical fault separation. |
Dual-redundant microcontrollers featuring EMI-insulated fiber-optic links. |
|
Voltage Regulation |
Standard transient recovery matching facility tolerance limits. |
Ultra-tight transient tolerance preventing downstream UPS engagement. |
Digital voltage regulators with pre-programmed cross-current compensation. |
Core Component Engineering & Integration
HPCR Injection Powertrain: High-pressure common rail diesel engine utilizes electronic unit injectors calibrated for precise combustion during sudden load variations.
Form-Wound VPI Alternator: Synchronous brushless alternator features form-wound stator coils with vacuum pressure impregnation to resist server-induced high-frequency harmonics.
Decentralized Controller Architecture: Networked microprocessors segregate control logic via dual-channel, shielded CAN-bus wiring to eliminate single-point signaling failures.
Dual-Pump Fuel Manifold: Twin-parallel primary filtration with manual changeover valves allows water separation and element replacement during continuous runtime.
Emissions & Environmental
Closed-Loop SCR Systems: Integrated selective catalytic reduction utilizes automated urea dosing to satisfy EPA Tier 4 requirements.
Active DPF Filtration: Wall-flow diesel particulate filters capture fine soot matter without inducing exhaust backpressure penalties.
Thermal Management Shutter: Motorized radiator louvers automatically regulate interior airflow to prevent cold-climate engine overcooling.
Bunded Fuel Containment: Double-walled sub-base structural tanks provide 110% fluid containment preventing localized soil contamination.
System Testing & Factory Acceptance Test (FAT)
100% Transient Load Testing
Verified via reactive load banks replicating 0-100% block loading for G3 compliance.
Hour Continuous Run
Monitored via digital sensors at 100% continuous DCP rating to verify thermal equilibrium.
Microsecond Synch Validation
Microprocessor-controlled paralleling tested to ensure multi-unit synchronization within 100 milliseconds.
Harmonic Distortion Analysis
Alternator THD certified under 5% non-linear load using integrated power quality analyzers.
High-Voltage Insulation Test
Stator windings subjected to 2,000V AC dielectric strength testing to ensure insulation integrity.
Remote Digital Witnessing
High-definition video stream and real-time telemetry exported for offsite third-party FAT auditing.
FAQ